MEASURED PARAMETERS Display Comms. Relays Optional
Analogs
Trigger
Setpoint
Alarm Pulse
True RMS Voltage (Volts L-L & L-N) Average RMS per Phase x x x   x x
Direct Voltage input: Up to 690 V L-L & 400 L-N Real-time per phase   x x      
PT Ratio: 1.0 - 6500.0 Min/Max per phase x x       x
Range of Reading: 1 - 999,000 V Voltage Unbalance   x     x x
Accuracy: +/- 0.25% FS              
True RMS Current (Amps) Average RMS per Phase x x x   x x
Secondary Current Input: 5A or 1A Real-time per phase   x x   x  
CT Ratio: 1 to 50,000 Min/Max per phase x x       x
Range of Reading: 0 - 60,000 A Current Unbalance   x     x x
Accuracy: +/- 0.25% FS              
Neutral Current (AMPS) Average RMS x x x   x x
Range of Reading: 0 - 60,000 A Real-time   x        
Accuracy: +/- 0.25% FS) Min/Max x x x     x
Frequency (Hz) Average RMS x x x   x x
Range of Reading: 45.00 to 55.00 Hz Real-time   x x   x x
Accuracy: +/-0.1% Reading Min/Max x x        
Power Factor (PF) Average total x x x   x x
Range of Reading: 0.0 to 1.000 Lead/Lag Average per phase x x       x
Accuracy: +/- 1% Reading Real-time total   x     x x
    Real-time per phase   x       x
    Min/Max total x x       x
Phase Rotation Positive, Negative, Error Pos, Neg, Err x   x      
POWER FUNCTIONS
Active Power (Watts) Average Total x x x   x x
Range of Reading: -2,000,000 to 2,000,000 kW Average per phase x x     x x
Accuracy: +/- 0.5% FS Real-time total   x x   x x
    Real-time per phase   x x   x x
    Min/Max total x x x     x
Reactive Power (vars) Average Total x x x   x x
Range of Reading: -2,000,000 to 2,000,000 kvar Average per phase x x x   x x
Accuracy: +/- 0.5% FS Real-time total   x     x x
    Real-time per-phase   x     x x
    Min/Max total x x       x
Apparent Power (VA) Average Total x x x   x x
Range of Reading: 0 to 2,000,000 kVA Average per phase x x     x x
Accuracy: +/- 0.5% FS Real-time total   x     x x
    Real-time per-phase   x     x x
    Min/Max total x x       x
ENERGY FUNCTIONS
Active Energy (MWh) Import x x x x    
Range of Reading: 0 - 99,999 MWh Export x x x x    
Accuracy: As Power Net x x x x    
    Total     x x    
Reactive Energy (Mvarh) Import x x x x    
Range of Reading: 0 - 99,999 MWh Export x x x x    
Accuracy: As Power Net x x x x    
    Total x x x x    
Apparent Energy (MVAh) Total x x x x    
Range of Reading: 0 - 99,999 MWh              
Accuracy: As Power              
DEMAND FUNCTIONS
Voltage Demand (Volts) Demand per phase x x x     x
(same as Voltage)   Max Demand per phase x x x     x
Current demand (Amps) Demand per phase x x x     x
(same as Current)   Max Demand per phase x x x     x
Active Power Demand (Watts) Block Demand x x x   x x
(same as Active Power)   Sliding Window Demand x x x   x x
    Thermal Demand x x x   x x
    Predicted Acc. Demand x x x   x x
    Predicted Sliding Demand x x x   x x
Reactive Power Demand (vars) Block Demand x x x   x x
(same as Reactive Power)   Sliding Window Demand x x x   x x
    Thermal Demand x x x   x x
    Predicted Acc. Demand x x x   x x
    Predicted Sliding Demand x x x   x x
Apparent Power Demand (VA) Block Demand x x x   x x
(same as Apparent Power)   Sliding Window Demand x x x   x x
    Thermal Demand x x x   x x
    Predicted Acc. Demand x x x   x x
    Predicted Sliding Demand x x x   x x
QUALITY OF SUPPLY FUNCTIONS
Harmonics                
Accuracy: +/- 1.5% FS Voltage THD per phase x x x     x
    Harmonic Volts Odd (1-39) x x x   x x
    Voltage Harmonics % (1-40)   x x   x x
    Current THD per phase x x x     x
    Harmonic Amps odd (1-39) x x x   x x
    Current Harmonics % (1-40)   x x   x x
    Harmonic kW Odd (1-39) x x x   x x
    Harmonic kvar Odd (1-39) x x x   x x
    Harmonic PF Odd (1-39) x x x   x x
    K-factor per phase x x x     x
ENERGY TIME OF USE FUNCTIONS
    8 Energy registers   x       x
    16 tariffs per register   x       x
    Max. Dem.TOU kW & kVA   x       x
ADDITIONAL FUNCTIONS
    Day & Time x x x     x
    Pulse Counters x x x     x
    Remote Relay Control   x        
    Digital Input Status x x       x
    Alarm Relay Status x x       x
    Alarm Trigger Status   x       x
    Self-diagnostic Tests x x        



OPTIONS Codes
VOLTAGE INPUTS
660V AC Nominal Voltage Input 0
120V AC Nominal Voltage Input U
CURRENT INPUTS
5 Ampere 5
1 Ampere 1
POWER SUPPLY
95-250V AC and 70-330V DC (Standard) ACDC
9-18V DC 1DC
18-36V DC 2DC
38-72V DC 3DC
ANALOG OPTION
No Analog Output 0
0-20mA (0-10-20) A2
4-20mA (4-12-20) A4
GROUND LEAKAGE or NEUTRAL CURRENT
No Ground Leakage or Neutral Current 0
Ground Leakage Current (5mA) L
Neutral Current 1Amp Input N1
Neutral Current 5Amp Input N5